Load Flow analysis

With EA-PSM Electric Load Flow function, one can calculate load flows in all kind of power systems from low and mid voltage distribution and industrial networks to high voltage transmission grids. Load Flow calsulation results are verified with various test case studies.lf

  • Automatically detects equipment overloads and voltage violations and allows to perform equipment sizing task with unmatchable efficiency and precision.
  • EA-PSM Electric Load Flow tool is optimized for design and maintenance engineers, it allows to complete common tasks faster with even higher quality, therefore, it saves time and money.
  • Enhanced models of two and three winding power transformers, reactors, induction motors and synchronous generators allows to simulate realistic power system conditions.

With EA-PSM Electric Load Flow function one can perform these common tasks:

 

Power factor correction Optimize system power flows Voltage regulation Fast and easy documentation
Design power factor correction system more efficiently and have the fastest payback time for your investments. Minimize power losses by efficiently distributing loads or by selecting the most suitable cable/overhead line and save your money. Adopt the most efficient techno-economical solution for voltage drop issue in the electrical system which includes transformer tap changing, generator reactive power regulation and connection of automatic voltage regulator. EA–PSM allows to export system data and calculation results to Microsoft Office® and AutoCAD®.

 


 

PARALLEL OPERATION OF ELECTRICAL POWER TRANSFORMERS

 

It is common schemato use several smaller rated transformers connected in parallel instead of one bigger rated transformer in electrical power systems. The advantages of parallel operation of transformers are:

  • Increased reliability and maximized electrical power system availability.

    This is because it is not necessary to disconnect the whole system if fault occurs with one of the transformers. What is more, system operators can disconnect any transformer for maintenance purpose, while other transformers will serve the load, therefore, this ensures continuous electric power supply.

  • Maximized electrical power system efficiency.

    Sufficiently good efficiency of a power transformer is within a wide loading range, from 50% to 100% of the rated transformer power. However, if loading is smaller, efficiency of a transformer decreases, therefore, in case several transformers are installed in parallel, it is possible to switch on only those transformers which will give the total demand by running only on efficient loading.

However, in order to connect two or more power transformers in parallel, several technical conditions have to be satisfied.

Same voltage ratio and identical position of tap changer

If two transformers of different voltage ratio (or tap changer position) are connected in parallel, there will be a difference in secondary voltages. Because of this, a circulating current between secondary and primary winding will appear. Internal impedance of transformer is small, therefore only a small voltage difference may cause a considerably high circulating current and additional losses. Vector diagram of two parallel transformers with different secondary voltages is depicted in Fig.1, circulating current is “I”.

pav1
Fig. 1 Vector diagram of parallel transformers secondary voltages. Here “I” is circulating current, “Udif” – voltage difference.

The presence of circulating current is also apparent in EA-PSM Electric calculations. In Fig. 2 between bus 3 and bus 4 current is not flowing because system is symmetrical and both transformers have identical parameters.

pav2
Fig. 2 Power flow calculation results of symmetrical system with two parallel transformers.

However, if we change, for example, a tap changer position in one of the transformers, the circulating current will flow between bus 3 and bus 4. This case is shown in Fig. 3 where transformer [T] Bus 2 – Bus 4 secondary winding voltage is increased by 10% and over 43  A current is present between bus 3 and bus 4.

Fig. 3 Power flow calculation results of unsymmetrical system. Here transformer T2 tap position is changed by 10%.
Fig. 3 Power flow calculation results of unsymmetrical system. Here transformer [T] Bus 2 – Bus 4 tap position is changed by

Same short circuit voltages

Power flows carried by parallel transformers are proportional to their MVA ratings if short circuit voltages of both transformers are equal. This relationship is shown by an equation:

lygtis

Where UkI and UkII are short circuit voltages, PI and PII power flows through transformers, SNI and SNII nominal powers (MVA) of transformers. In Fig. 4 transformer [T] Bus 1 – Bus 3 has a lower short circuit voltage, however, as both transformers have the same MVA rating, power distribution between transformers is not equal and [T] Bus 1 – Bus 3 is loaded more than[T] Bus 2 – Bus 4.

pav4
Fig.4 Transformer [T] Bus 1 – Bus 3 is loaded more than [T] Bus 2 – Bus 4, because its short circuit voltage is smaller.
 

Same phase sequence

The phase sequence of parallel transformers must be equal. Otherwise, during the cycle, each pair of phases will be short circuited.

Same phase angle shift (vector group)

Vector group of a transformer is determined in accordance with the phase displacement between line voltages of secondary windings. If two transformers with different vector groups are connected, a circulating current occurs as shown in a vector diagram in Fig. 5, what is more, if transformers with opposite voltage vectors are connected, this will produce short circuit conditions. Therefore, only transformers with the same vector groups can be connected. In EA – PSM Electric parallel connection of transformers with different vector groups is considered impossible.

pav5
Fig. 5 Vector diagram of parallel connected transformers with different phase angle shift.

Different system impedance

It is important to notice that if impedance of parallel system branches are not equal, loop power flows will occur despite other requirements are satisfied.